TD324Y interrupteur sous vide
Informations de base
Modèle: VITD 12/1250-20Y
Description du produit
Interrupteur sous vide
VITD 12/1250-20Y
ELECTRICAL RATINGS(3PHASE) SYMMETRICAL BASIS | |
1.Rated Frequency | 50/60Hz |
2.Rated Maximum Line to Line Voltage | 12kV,r.m.s |
3.Rated Power Frequency Withstand Voltage:Air | 42kV,r.m.s |
4.Rated Impulse Withstand Voltage:Air | 95kV,Peak |
5.Rated Normal Current | 1250A |
6.Rated Short-Circuit Current(3Phase Symmetrical Basis) | 20kA,r.m.s |
7.Percentage D.C. Component of Rated S.C. Breaking Current | 50% |
8.Rated Short-Circuit Making Current | 50kA,Peak |
9.Rated Duration of Short Time Current | 4s |
10.Rated Short-Time Withstand Current | 20kA,r.m.s |
11.Rated Peak Withstand Current | 50kA,r.m.s |
12.*Maximum Contact Resistance at Minimum Closing Force | 19Micro ohms |
13.*Rated Breaking Current of Single Capacitor Bank | 630A,r.m.s |
14.*Rated Breaking Current of Back-to-Back Capacitor Bank | 400A,r.m.s |
15.Rated operating sequence | o-0.3s-co-180s-co |
MECHANICAL DATA | |
1.Interrupter Weight(Approx.) | 3.31kg |
2.Moving Part Weight(Approx.) | 1.2kg |
3.Closing Force due to Bellow and Atmospheric | 8040N |
4.Force Required to Hold Contacts open at Full Stroke | 12050N |
MECHANICAL REQUIREMENTS(REF. VCB) | |
1.Contact Stroke | 111 mm |
2.Opening Speed(average of 75 contact gap) | 1.10.2m/Sec |
3.Maximum Overtravel During Opening | 2mm |
4.Maximun Rebound During Opening | 2mm |
5.Closing Speed(average of last 30% contact gap) | 0.60.2m/Sec |
6.Maximum Contact Bounse Duration(with maximum 2 bounces) | 2ms |
7.Rated Contact Compressive Force | 2000200N |
8.Closing and Opening non-simultaneity of three-phase Contacts | 2ms |
LIFE (ESTIMATED) | |
1.Electrical Life at Rated Normal Current | 50,000Operations |
2.Electrical Life at Rated Short Circuit Current | 100Operations |
3.Mechanical Life | 50,000Operations |
4.Contact Erosion Limit | 3mm |
5.Shelf Life | 20Years |
1.Meets or exceeds the electrical endurance requirements of class E2 for autoreclosing duty per IEC 62271-200 and JB 8738-2008. 2.* Rated Characteristics to be given on request |
Groupes de Produits : Interrupteur sous vide
Premium Related Products
autres produits
Produits phares
TD324P interrupteur sous videTD324Y interrupteur sous videTD325J interrupteur sous videTD325K interrupteur sous videTD325Y interrupteur sous videTD326E interrupteur sous videTD326Y interrupteur sous videTD336G interrupteur sous videTD336Y interrupteur sous videTD358Y interrupteur sous videTD368Y interrupteur sous videTD424B interrupteur sous videTD425Y interrupteur sous videTD445Z interrupteur sous videTD524A interrupteur sous videTD544H interrupteur sous vide